FIRE RESISTANT WALL SYSTEMS
Technical Data :
eurekaWALL™
eurekaWALL™
System
Fire-Rating
FRL (mins)
(Test Ref.)
Construction Detail
Description (EurekaWall™ membrane plus)
Acoustic RAting
EWall
1
N/A
EurekaWALL™1 13mm Boral standard core plasterboard
Rw = 35dB
Rw + Ctr = 32dB
Non Load Bearing
/120/90 (basis FCO-2110)
EurekaWALL™1 13mm Boral FireStop™ plasterboard
Rw = 36dB
Rw + Ctr = 33dB
Non Load Bearing
EWall
2 (1)
/120/90 (basis FCO-2110)
EurekaWALL™2 As for EWall 1 with FireStop™, 20mm separation, independent stud wall, layer of 13mm Boral standard core plasterboard.
Rw = 56dB (2)
Rw + Ctr = 47dB (2)
(Insulation of 75GW14
or
75PE14) (3)
Non Load Bearing
EWall
3 (1)
-/120/90 (basis FCO-2110)
EurekaWALL™3 To each side an independent stud wall, layer of 13mm Boral FireStop™ and 20mm separation.
Rw = 63dB (2)
Rw + Ctr = 49dB (2)
(Insulation of 75GW14
or
75PE14) (3)
Non Load Bearing
EWall
4 (1)
-/120/90 (basis FCO-2110)
EurekaWALL™4 To one side an independent stud wall, layer of 13mm Boral FireStop™ and 20mm separation. To the other side, furring channels and layer of 13mm Boral FireStop™.
Rw = 55dB (2)
Rw + Ctr = 43dB (2)
(Insulation of 75GW14
or
75PE14) (3)
Non Load Bearing
Note:
(1) Max wall height is 3000mm based on 64CS50 studs @ 450mm centres with noggings or 2700mm based on 64CS50 studs @ 600mm centres with noggings. (2) Acoustic ratings based on independent stud wall cavity of 84mm. (3) 75GW14 = 75mm glasswool blanket/batt, nom 14kg/m3. 75PE14 = 75mm polyester blanket/batt, nom 14kg/m3.