CEILING BATTENS
Technical Data :
Lysaght Topspan® 40
Lysaght Topspan® 40
Schematic
LYSAGHT TOPSPAN® 40 battens are manufactured from BlueScope ZINCALUME® steel complying with AS1397-G550-AZ150 (550MPa minimum yield strength, 150g/m2 minimum coating mass)
Thickness (BMT)
0.55
Yield strength (MPa)
550
Coating Mass (g/m2)
150
Mass (kg/m)
0.62
Spanning Tables
Allowable Batten Spacing In Non-Cyclonic Areas
Notes:
These tables are based on a general design approach. The tables will give a practical and economic solution for most domestic buildings in non-cyclonic areas. For specific design situations, information on fastener and batten capacity may be obtained from our Technical Advisory Service on 1800 641 417.
The design pressures have been determined from AS1170 Part 2, 1989, Section 3, for buildings up to 6 metres high with pressure coefficients of +0.2 internally and 0.9 externally with a local pressure factor of 1.5.
Fastener selection for sheet roof:
For pine 2 off 12 11 x 40 Type 17 per joint
W28 minimum Truss chord material 1.0 BMT: 2 off 10 16 x 16*
W33 minimum Truss chord material 1.0 BMT: 2 off 10 16 x 16*
W41 minimum Truss chord material 1.0 BMT: 2 off 10 16 x 16*
W50 minimum Truss chord material 1.2 BMT: 2 off 12 - 14 x 20*
W60 minimum Truss chord material 1.2 BMT: 2 off 12 14 x 20*
W70 minimum Truss chord material 1.6 BMT: 2 off 12 14 x 20*
* Hex. Self-drilling screws
Fastener selection for tile roofing: 1 off 10 16 x 16 Hex. Self drilling screws per joint alternating top and bottom. Use 2 per joint at free ends.
Fastener selection for cladding: 12 gauge Type 17 or 12 11 reduced drill point as per standard recommendations.
The maximum batten span is 1200 mm for sheet or tile roofing.
Roof truss design may be based on a maximum batten spacing. The designer / fabricator should be contacted for this information. LYSAGHT® truss designs have 1200 mm maximum batten spacing.
Batten overhang using TOPSPAN® 40 should not exceed 300 mm without engineering approval.
The tables have been determined based on the following assumptions:
the batten is continuous over at least 3 spans;
all trusses are uniformly spaced;
fastener pullout loads determined for batten to Z chord connection
For sheet roofing applications, batten connections to the chord of the first truss in from the gable end will require strapping if the batten spacing is less than 2366 mm and the truss spacing is 450 mm. Strapping shall be 1.0 x 25mm fastened to the web of the truss chord with 2 off 10 16 x 16 Hex. Self-drilling screws.
DESIGN WIND SPEED
W28
W33
W41
ROOF CLADDING
BMT (mm)
Span Type
Truss Spacing
Truss Spacing
Truss Spacing
600
900
1200
600
900
1200
600
900
1200
LYSAGHT
CUSTOM ORB®
0.42
END
900
900
900
900
900
900
900
900
900
INT
1200
1200
1200
1200
1200
1200
1200
1200
1000
0.48
END
1200*
1200*
1200*
1200*
1200*
1200*
1200*
1200*
1000*
INT
1600*
1600*
1600*
1600*
1600*
1540*
1600*
1330*
1000*
LYSAGHT
CUSTOM BLUE ORB®
0.60
END
900
900
900
900
900
900
900
900
900
INT
1200
1200
1200
1200
1200
1200
1200
1200
1000
0.80
END
1800*
1800*
1800*
1800*
1800*
1540*
1800
1330*
1000*
INT
2400*
2400*
2150*
2400*
2060*
1540*
2000*
1330*
1000*
LYSAGHT
TRIMDEK®
0.42
END
1000
1000
1000
1000
1000
1000
1000
1000
1000
INT
1700
1700
1700
1700
1700
1540
1700
1330
1000
0.48
END
1700
1700
1700
1700
1700
1540
1675
1330
1000
INT
2300
2300
2150
2300
2060
1540
2000
1330
1000
LYSAGHT
SPANDEK®
0.42
END
1500
1500
1500
1500
1500
1500
1500
1330
1000
INT
2100
2100
2100
2100
2060
1540
2000
1330
1000
0.48
END
1950
1950
1950
1950
1950
1540
1940#
1330
1000
INT
2800
2800
2150
2800
2060
1540
2000
1330
1000
LYSAGHT
KLIP-LOK®
0.42
END
1200
1200
1200
1200
1200
1200
1200
1200
1000
INT
1300
1300
1300
1300
1300
1300
1300
1300
1000
0.48
END
1800
1800
1800
1800
1800
1540
1800
1330
1000
INT
2100
2100
2100
2100
2060
1540
2000
1330
1000
0.60
END
2300
2300
2150
2300
2060
1540
2000
1330
1000
INT
2700
2700
2150
2700
2060
1540
2000
1330
1000
LYSAGHT
KLIP-LOK® 700
0.42
END
1100
1100
1100
1100
1100
1100
N.R.
N.R.
N.R.
INT
1300
1300
1300
1300
1300
1300
N.R.
N.R.
N.R.
0.48
END
1800
1800
1800
1800
1800
1540
1800
1330
1000
INT
2100
2100
2100
2100
2060
1540
2000
1330
1000
Notes:
END = End Span
INT = Internal Span
* 5 fasteners per sheet
# 4 fasteners per sheet
N.R. Not Recommended
Capacity & Load Tables
Maximum Safe Loads (kN/m)
Span
Single Span
Double Span
Continuous Span
(mm)
Wi
Wo
Wd
Wi
Wo
Wd
Wi
Wo
Wd
600
5.73
4.16
4.70
5.73
4.16
11.34
6.51
3.78
6.51
900
2.54
2.54
1.39
2.54
2.54
3.36
2.89
2.52
2.89
1200
1.43
1.43
0.58
1.43
1.43
1.42
1.62
1.62
1.62
1500
0.92
0.92
0.30
0.92
0.92
0.72
1.04
1.04
1.04
1800
0.64
0.64
0.17
0.64
0.64
0.42
0.72
0.72
0.72
2100
0.47
0.47
0.11
0.47
0.47
0.26
0.53
0.53
0.53
2400
0.35
0.35
0.07
0.35
0.35
0.18
0.40
0.40
0.40
Notes:
Wi = Maximum Allowable Inward Load
Wo = Maximum Allowable Outward Load
Wd = Load to cause Span/300 deflection
Two (2) fasteners at the supports - No.12-14x20 Tek Hex Head Screws
Minimum support thickness of 1.0mm BMT
Loads are in kN/m
Maximum span for roof batten or purlin is 1200mm (limited by 1.1kN point load).
Section Properties
Product
Thickness (BMT mm)
Area (mm2)
Section Modulus (mm3)
Second Moment of Area (103mm4)
Zx
Zy
Ix
Iy
LYSAGHT TOPSPAN® 40
0.55
83
969
1080
20.6
39.7
0.75
113
1320
1475
28.1
54.1
Please note that the section modulus and secnd moment of area are both calculated about the principal axes.
For further information please download Lysaght's Topspan 40 Product Brochure. It is available from below in a PDF format.